| Adjustment Range | 0.8 leading-0.8 lagging | ||||
| Total Current Harmonic Distortion THDi | <3% (of nominal power) | ||||
| DC Injection Current | <0.5%ln | ||||
| Efficiency | |||||
| Max Efficiency | 97.60% | ||||
| Euro Efficiency | 97.0% | ||||
| MPPT Efficiency | >99% | ||||
| Equipment Protection | |||||
| DC Polarity Reverse Connection Protection | YES | ||||
| AC Output Overcurrent Protection | YES | ||||
| AC Output Overvoltage Protection | YES | ||||
| AC Output Short Circuit Protection | YES | ||||
| Thermal Protection | YES | ||||
| DC Terminal Insulation Impedance Monitoring | YES | ||||
| DC Component Monitoring | YES | ||||
| Ground Fault Current Monitoring | YES | ||||
| Power Network Monitoring | YES | ||||
| Island Protection Monitoring | YES | ||||
| Earth Fault Detection | YES | ||||
| DC Input Switch | YES | ||||
| Overvoltage Load Drop Protection | YES | ||||
| Residual Current (RCD) Detection | YES | ||||
| Surge Protection Level | TYPE II(DC), TYPE II(AC) | ||||
| Interface | |||||
| Communication Interface | WIFI, RS485, CAN | ||||
| General Data | |||||
| Operating Temperature Range | -40℃+60℃,>45℃ Derating | ||||
| Permissible Ambient Humidity | 0-100% | ||||
| Permissible Altitude | 2000m | ||||
| Noise | ≤ 65 dB(A) | ||||
| Ingress Protection(IP) Rating | IP 65 | ||||
| Inverter Topology | Non-Isolated | ||||
| Over Voltage Category | OVC II(DC),OVC III(AC) | ||||
| Cabinet size(W*H*D)[mm] | 527*894*294(Excluding connectors and brackets) | ||||
| Weight[kg] | 80 | ||||
| Warranty | 5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
||||
| Type Of Cooling | Intelligent air cooling | ||||
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 |
||||
| Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||||